The extinguisher beside the lift on the ninth floor carries a paper tag with a refill date. In some towers that date is years old and nobody has noticed, because a fire system gives no sign that it has stopped working until the night it is needed. The fire audit every housing society in Maharashtra owes is the check meant to notice: a licensed agency's certificate, called Form B, furnished to the fire authority every January and July. In Pune, the city's chief fire officer said in 2025 that only 10 to 15 percent of housing societies had filed it.

Key takeaways

  • Section 3(3) of the Maharashtra Fire Prevention and Life Safety Measures Act, 2006 requires the owner or occupier of a building to furnish a licensed agency's certificate in Form B, on the maintenance of its fire systems, in January and July every year.
  • Form A is the agency's certificate when the fire systems are first installed; Form B is the twice-yearly certificate that they are still maintained and working.
  • In a completed tower the duty falls in practice on the co-operative housing society, which appoints the agency, pays for the inspection and the repairs, and furnishes the certificate.
  • Amendment rules notified on 12 June 2025 let the owner or occupier furnish the certificate in person, by registered post, by courier or online.
  • A member can ask the committee in writing for the last two Form B certificates and the fire authority's acknowledgement, and a resale buyer should ask for the same before signing.

What the law asks, and of whom

Maharashtra's fire law is the Maharashtra Fire Prevention and Life Safety Measures Act, 2006, with the Maharashtra Fire Prevention and Life Safety Measures Rules, 2009 made under it. Section 3 of the Act puts the fire prevention and life safety measures of a building on its owner or occupier. Two certificates from a licensed agency follow from that duty. Form A is given when the measures are installed. Form B, under section 3(3), is the maintenance certificate, and it is furnished to the Chief Fire Officer or the Director of Fire Services in January and July every year. The Directorate's own format for submitting it cites section 3 of the Act and rule 4 of the 2009 Rules.

The rules were amended on 12 June 2025. The amendment provides for automated continuous monitoring of a building's fire-fighting systems and allows certificates to be furnished in person, by registered post, by courier or online.

The Act speaks of the owner or occupier. In a completed tower whose common parts the society runs, that is in practice the society: no single flat owner can service the fire pump or test the riser. Until the promoter hands the building over, ask the promoter who is furnishing Form B. After the handover, it is the managing committee's job, paid for from the maintenance every member contributes.

DocumentWho issues itWhenWhat it tells you
Provisional fire NOCThe fire authorityAt the plan stageThat the design was accepted, not that anything was built
Final fire NOCThe fire authorityAfter the installations are in and testedThat the systems worked when the building was finished
Form AA licensed agencyWhen the measures are first installedThat the installation was complete
Form BA licensed agencyEvery January and JulyThat the systems are still maintained and working now

Only the last row speaks to the present. The others describe the day the building was finished, which for a tower ten years old is a long time ago.

How often a check finds something

The figures that exist suggest the inspection is not a formality. In July 2024 the Chief Minister told the Maharashtra Legislative Council, in a written reply reported by Deccan Herald, that Mumbai had recorded about 13,000 fire incidents in three years, in which 65 people died, and that fire safety audits of 1,270 buildings had found deficiencies in 278 of them.

Mumbai buildings given a fire safety audit, and those found deficient(buildings)
Buildings audited1,270
Deficiencies found278

Source: Chief Minister's written reply in the Maharashtra Legislative Council, as reported by Deccan Herald, July 2024

That is more than one building in five. Filing is rarer still in Pune.

10 to 15%
Share of Pune's housing societies that had filed Form B, according to the city's chief fire officer.

Source: Pune Fire Brigade, as reported by Pune Pulse, 2025

What you need before you start

A member checking whether the society files, or a buyer checking a resale flat, needs four things.

  • The last two Form B certificates, one dated January and one July, with the agency's name and licence number on them.
  • The fire authority's acknowledgement of each: an inward stamp, a registered post receipt, or the online submission receipt.
  • The managing committee minutes that appointed the agency and approved its bill. These are records a member may inspect and copy, as housing society member rights explains.
  • A list of what your building has: hose reels, a wet riser, sprinklers, alarms, a fire pump. The final fire NOC or the Form A usually describes it.

The steps

One Form B cycle in a housing society
  1. 1

    1. Appoint a licensed agency

    The committee compares quotations from agencies licensed under the Act and records its decision in the minutes.

  2. 2

    2. Inspect and test

    The agency runs the pumps, checks pressure at the risers and hose reels, tests alarms and detectors, and checks extinguishers, fire doors and exits.

  3. 3

    3. Repair what failed

    Defects are fixed before the certificate is signed. An agency that certifies what is not working puts its own licence at risk.

  4. 4

    4. The agency issues Form B

    The certificate names the building, the measures checked and the agency's licence.

  5. 5

    5. Furnish it in January or July

    To the Chief Fire Officer or the Director of Fire Services, in person, by registered post, by courier or online.

  6. 6

    6. Keep the acknowledgement and repeat

    File the receipt with the certificate, show members on request, and start the next cycle in six months.

Source: Maharashtra Fire Prevention and Life Safety Measures Act, 2006, s.3(3) and s.9(4); Rules, 2009, rule 4, as amended on 12 June 2025

1. Find out who files today. In a building still run by the promoter, write to the promoter; in one the society has taken over, write to the secretary. You should get a name and a date. The red flag is each side pointing at the other, which is common in the year after handover that from possession to society describes.

2. Ask in writing for the last two certificates and their acknowledgements. You should see two Form B certificates six months apart. The red flag is a certificate with no proof it ever reached the fire authority, or one from three years ago.

3. Check the agency. Note its licence number and ask whether the licence was valid on the certificate's date. The red flag is a certificate on a maintenance contractor's letterhead with no licence number at all.

4. Read what was checked. A certificate that lists the pumps, risers, hose reels, alarms and extinguishers is a record of an inspection. The red flag is a one-line certificate that names none of them.

5. Walk the building yourself. Look at the extinguisher tags, the hose reel cabinets, the fire doors on the staircase and the refuge area if your tower has one. The safety rules you can check without help are set out in lifts, refuge areas and exits. The red flag is a staircase used for storage or a fire door wedged open, whatever the certificate says.

6. If nothing was filed, take it to the general body. Ask for the appointment of an agency to be placed on the agenda. One member cannot appoint an agency; a resolution can.

An analogy: the PUC certificate on your car

A car's pollution-under-control certificate is issued by an authorised centre after a test, carries a date, and has to be renewed on a schedule whether or not anything seems wrong. Form B works the same way for a building: an authorised agency tests, certifies a date, and the clock starts again. The difference is that nobody stops a building at a signal and asks to see its certificate. The members are the only people who routinely ask.

Suresh and Kavita's first Form B

Suresh and Kavita (illustrative, as our stories always are) live in their Pune retirement flat in a tower of 64 flats that has its own co-operative housing society. After the society's first general body meeting in September, Suresh, who asks for papers in writing as a habit, wrote to the secretary asking for the July Form B and its acknowledgement. The answer was that there was none. The promoter's licensed agency had given Form A when the systems were commissioned, and since the handover nobody had appointed anyone. Kavita, who is secretary of the separate buyers' association for the registration's unfinished towers and not of this society, helped him draft the letter. Names and numbers in this story are illustrative.

The committee asked three licensed agencies for quotations and appointed one in October for Rs 18,000. Its team spent two days in the building. The fire pump started, but the smaller jockey pump that keeps the pipes under pressure was cycling because of a faulty pressure switch. Two hose reel nozzles were missing, five extinguishers were past their refill dates, the alarm panel at the security cabin showed a fault on one floor, and the door closer on a staircase fire door had failed. The repairs cost Rs 46,500, so the cycle came to Rs 64,500, about Rs 1,000 a flat. The certificate was furnished online with the acknowledgement printed and filed, late for July, and the committee minuted that the next one is due in January.

What the members learned mattered more than the bill. The fire pump is a different machine from the two water pumps the society replaced earlier in the year, and it had never been run since the handover. Nobody on the committee had known where the alarm panel was.

When a society does not file

The Act treats a failure here as more than a missed deadline. Section 36 makes contraventions an offence, and section 8 gives the authorities a power to seal premises. Pune's fire brigade has warned that a building that does not furnish Form B in time leaves its owner or occupier solely responsible if there is a mishap, and that non-compliant buildings risk the suspension of water and electricity supply.

Warning

A Form B is only as good as the inspection behind it. An agency that issues one without the measures actually being in place risks suspension or cancellation of its licence under section 9(4) of the Act. A committee that pays for a certificate and skips the repairs has paid for paper, and it is the members who live above the pump that does not start.

The money comes from the same maintenance every member pays, which is why a fire cycle belongs in the budget the general body passes. How the heads of a maintenance bill are lawfully set, and the repair fund this draws on, is in maintenance charges in Maharashtra. The society's building insurance is a separate question, set out in home insurance for a flat.

Buying a resale flat: ask for the last two

A resale buyer joins the society and inherits whatever it has not done. Two consecutive Form B certificates with acknowledgements tell you the systems were tested twice in the last year and that the committee runs a calendar. Their absence tells you a repair bill may be waiting, and that you would be paying your share of it. In an older building, ask for them alongside the structural audit report; both are records of how the building is being kept.

What the register can and cannot tell you

Form B certificates and fire NOCs do not sit on MahaRERA, so no report built from the register can say whether a society files. What the filing does answer is the tower you are joining. For a Maharashtra project, the Rs 499 ReraGenie buyer report sets out the permission chain, including whether the occupancy certificate slot holds a document and its upload date (an upload, not proof the certificate was granted, as completion and occupancy certificates explains); the sanctions, units and sales building by building, which tell you how many flats share the systems and the bills; and the complaints and cases filed against the project, in plain words.

If you are still choosing a tower and the fire systems are part of the worry, start with the project's free page on ReraGenie, which shows every filed document and its upload date, so you know what to ask the society for before you pay a booking amount.

The checklist, in one place

  • Ask who furnishes Form B today: the promoter before handover, the society after.
  • Get the last two certificates, one January and one July, with the fire authority's acknowledgement of each.
  • Check the agency's licence number and its validity on the certificate's date.
  • Read what the certificate lists; a one-line certificate is a red flag.
  • Walk the staircase, the fire doors, the hose reels and the extinguisher tags yourself.
  • If nothing was filed, ask for an agency's appointment on the general body agenda.
  • Buying resale, ask for the two certificates before you sign.

Methodology and sources

  • Maharashtra Fire Prevention and Life Safety Measures Act, 2006: section 3 (the owner or occupier's duty), section 3(3) (Form B in January and July), section 8 (sealing), section 9(4) (licensed agencies), section 36 (offences).
  • Maharashtra Fire Prevention and Life Safety Measures Rules, 2009, rule 4, as cited in the Directorate of Maharashtra Fire Services' Form B format; Amendment Rules, 2025, notified on 12 June 2025.
  • Mumbai fire incidents and audits: the Chief Minister's written reply in the Maharashtra Legislative Council, as reported by Deccan Herald, July 2024.
  • Pune Form B filing and the fire brigade's warnings: Pune Pulse, reporting the Pune Fire Brigade, 2025.

This article is educational and not legal advice. For a dispute, consult a lawyer who practices before your state's RERA.

Evaluating a project right now?

The ReraGenie buyer report reads every filing for one project and sets out the red flags, the checks that came back clear and what to verify before you book, each fact with its filing date. Rs 499, one time.

See the buyer report